ICS Alert

Sinapsi eSolar Light Vulnerabilities

Last Revised
Alert Code
ICS-ALERT-12-284-01

Description

This alert describes a public report of four vulnerabilities with proof-of-concept (PoC) exploit code affecting the Sinapsi eSolar Light Photovoltaic System Monitor, a supervisory control and data acquisition (SCADA) monitoring product.

table.gridtable {
font-family: verdana,arial,sans-serif;
font-size:11px;
color:#333333;
border-width: 1px;
border-color: #666666;
border-collapse: collapse;
}
table.gridtable th {
border-width: 1px;
padding: 8px;
border-style: solid;
border-color: #666666;
background-color: #dedede;
}
table.gridtable td {
border-width: 1px;
padding: 8px;
border-style: solid;
border-color: #666666;
background-color: #ffffff;
}

Summary

ICS-CERT is aware of a public report of four vulnerabilities with proof-of-concept (PoC) exploit codeVulnerabilities in Ezylog photovoltaic management server, http://www.exploit-db.com/exploits/21273/, Web site last accessed October 10, 2012. affecting the Sinapsi eSolar Light Photovoltaic System Monitor, a supervisory control and data acquisition (SCADA) monitoring product. According to the vendor’s website,b the company is based in Italy. The product has also been also sold as the Enerpoint eSolar Light, Schneider Electric Ezylog Photovoltaic Management Server, Gavazzi Eos-Box, and Astrid Green Power Guardian.

According to researchers Roberto Paleari and Ivan Speziale, the vulnerabilities are exploitable remotely by authenticating to the service using hard-coded credentials. Exploitation of these vulnerabilities would allow attackers to remotely connect to the server and executing remote code, possibly affecting the availability and integrity of the device. This report was released without coordination with either the vendor or ICS-CERT.

ICS-CERT has notified the affected vendor of this report and has asked the vendor to confirm the vulnerability and identify mitigations. ICS-CERT is unaware of any validated mitigations or workarounds at this time. This product is used in the Energy Sector. ICS-CERT is issuing this alert to provide early notice of the report and identify baseline mitigations for reducing risks to these and other cybersecurity attacks.

The report included vulnerability details and PoC exploit code for the following vulnerabilities:

Vulnerability Type Remotely Exploitable Impact
Hard-coded Credentials Yes Unauthorized Authentication
SQL Injection Yes Information Leakage
Command Execution Yes Remote Code Execution
Broken Session Enforcement Yes Unauthorized Authentication

Please report any issues affecting control systems in critical infrastructure environments to ICS-CERT.

Mitigations

ICS-CERT is currently coordinating with the vendor and security researchers to identify mitigations.

ICS-CERT recommends that users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should perform the following.

  • Minimize network exposure for all control system devices. Control system devices should not directly face the Internet.ICS-CERT ALERT, http://ics-cert.us-cert.gov/alerts/ICS-ALERT-10-301-01, Web site last accessed October 10, 2012.
  • Locate control system networks and devices behind firewalls, and isolate them from the business network.
  • If remote access is required, employ secure methods, such as Virtual Private Networks (VPNs), recognizing that VPN is only as secure as the connected devices.

ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to taking defensive measures.

ICS-CERT also provides a recommended practices section for control systems on the US-CERT Web site. Several recommended practices are available for reading or download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Organizations that observe any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.

Mitigations

Follow-Up

ICS-CERT released a follow-up advisory ICSA-12-325-01 Sinapsi Devices Vulnerabilities to the ICS-CERT Web page on
November 20, 2012.

This product is provided subject to this Notification and this Privacy & Use policy.

Vendor

Sinapsi