All information products included in http://ics-cert.us-cert.gov are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see http://www.us-cert.gov/tlp/.



SUMMARY

An independent researcher has published eight vulnerabilities with exploit code in RealFlex Technologies’ RealWin Supervisory Control and Data Acquisition (SCADA) product. Multiple functions listening on 910/TCP and 912/TCP are susceptible to heap and stacked-based buffer overflow vulnerabilities. The heap and stack buffer overflows may allow remote execution of arbitrary code.

ICS-CERT is currently coordinating with the vendor and security researcher to identify additional mitigations. ICS-CERT will provide additional information as it becomes available.

FOLLOW-UP

ICS-CERT released vulnerability details and mitigation recommendations in the follow-up advisory, ICSA-11-110-01 RealFlex RealWin Vulnerabilities, on May 06, 2011.

MITIGATION

ICS-CERT recommends that users minimize network exposure for all control system devices. Control system devices should not directly face the Internet.a Locate control system networks and devices behind firewalls, and isolate them from the business network. If remote access is required, employ secure methods such as Virtual Private Networks (VPNs).

Organizations that observe any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents. ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to taking defensive measures.

The Control System Security Program also provides a recommended practices section for control systems on the US-CERT website. Several recommended practices are available for reading or download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

BACKGROUND

RealWin is a SCADA server that includes a human-machine interface (HMI) application. It runs on Microsoft Windows platforms (2000 and XP). It can run on a single system or on multiple PCs connected through a TCP/IP network.

RealFlex was established in 1982 and has offices in Limerick, Ireland; Houston, Texas; and Saratov, Russia. RealFlex products are used in more than 45 countries with primary sectors being power, oil and gas, water and wastewater, marine, transport, chemical, manufacturing, and telecommunications.


Contact Information

For any questions related to this report, please contact the NCCIC at:

Email: NCCICCUSTOMERSERVICE@hq.dhs.gov
Toll Free: 1-888-282-0870

For industrial control systems cybersecurity information:  http://ics-cert.us-cert.gov 
or incident reporting:  https://ics-cert.us-cert.gov/Report-Incident?

The NCCIC continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.

Was this document helpful?  Yes  |  Somewhat  |  No

Back to Top