All information products included in http://ics-cert.us-cert.gov are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see http://www.us-cert.gov/tlp/.



Summary

ICS-CERT is aware of reports describing a vulnerability in SCADA Engine’s BACnet OPC Client, which could be used for arbitrary code execution. The vulnerability is reportedly due to a boundary error in WTclient.dll when preparing a status log message. This can be exploited to create a stack-based buffer overflow when a user opens a specially crafted file (e.g., *.csv file). This vulnerability has been reported to be confirmed in Version 1.0.24. However, other versions may also be affected. ICS-CERT is in the process of confirming these reports with the vendor.

The BACnet protocol was developed by ASHARE and is generally used for Building Automation and Control systems. It has been implemented by many manufacturers of Building Automation products. The SCADA Engine BACnet OPC Client supports OPC Data Access Specification 1.0 and 2.0 and Event/Alarm Specification 1.0. Supported operating systems are Windows NT 4.0, Windows 2000, and Windows XP.

ICS-CERT is not currently aware of a workaround or patch for this vulnerability. ICS-CERT recommends industrial control systems owners and operators take extreme caution when opening unexpected or untrusted files, especially *.csv files. ICS-CERT is in the process of contacting the vendor and will provide updates as appropriate.

Followup

ICS-CERT released vulnerability details and mitigation recommendations in the follow-up advisory, ICSA-10-264-01 SCADA Engine BACnet OPC Client Vulnerability, on September 21, 2010.

Please report any issues affecting control systems in critical infrastructure environments to ICS-CERT.

Other resources:
http://secunia.com/advisories/41466
http://www.bacnet.org/


Contact Information

For any questions related to this report, please contact the NCCIC at:

Email: NCCICCUSTOMERSERVICE@hq.dhs.gov
Toll Free: 1-888-282-0870

For industrial control systems cybersecurity information:  http://ics-cert.us-cert.gov 
or incident reporting:  https://ics-cert.us-cert.gov/Report-Incident?

The NCCIC continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.

Was this document helpful?  Yes  |  Somewhat  |  No

Back to Top