U.S. Flag Official website of the Department of Homeland Security
U.S. Department of Homeland Security Seal. ICS-CERT. Industrial Control Systems Cyber Emergency Response Team.
TLP:WHITE

Advisory (ICSA-18-088-01)

WAGO 750 Series

Original release date: March 29, 2018

Legal Notice

All information products included in http://ics-cert.us-cert.gov are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see http://www.us-cert.gov/tlp/.



CVSS v3 5.3

ATTENTION: Exploitable remotely/low skill level to exploit.

Vendor: WAGO

Equipment: 750 Series

Vulnerability: Improper Resource Shutdown or Release

AFFECTED PRODUCTS

The following versions of 750 series PLC are affected:

  • 750-880 firmware version 10 and prior,
  • 750-881 firmware version 10 and prior,
  • 750-852 firmware version 10 and prior,
  • 750-882 firmware version 10 and prior,
  • 750-885 firmware version 10 and prior,
  • 750-831 firmware version 10 and prior,
  • 750-889 firmware version 10 and prior, and
  • 750-829 firmware version 10 and prior.

IMPACT

Successful exploitation of this vulnerability could allow a denial-of-service condition affecting the ability of the device to establish connections to commissioning and service software tools.

MITIGATION

WAGO has released new firmware addressing this vulnerability that can be obtained by contacting WAGO support via email at support@wago.com.

If updating the firmware is not feasible WAGO recommends that users disable the WAGO Service Communication via WBM or limit the access to Ports 6626 and 2455/TCP/IP to trusted devices.

For more information see WAGO’s security advisory:
Vulnerability-in-the-WAGO-Ethernet-TCP-IP-driver.pdf

NCCIC recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:

  • Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
  • When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.

NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available in the NCCIC Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.

No known public exploits specifically target this vulnerability.

VULNERABILITY OVERVIEW

A remote attack may take advantage of an improper implementation of the 3 way handshake during a TCP connection affecting the communications with commission and service tools. Specially crafted packets may also be sent to Port 2455/TCP/IP, used in Codesys management software, which may result in a denial-of-service condition of communications with commissioning and service tools.

CVE-2018-8836 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L).

RESEARCHER

Younes Dragoni of Nozomi Networks reported the vulnerability to NCCIC.

BACKGROUND

Critical Infrastructure Sectors: Commercial Facilities, Critical Manufacturing, Energy, and Transportation Systems

Countries/Areas Deployed: Worldwide

Company Headquarters Location: United States, Germany, Switzerland, Poland, China, and India


Contact Information

For any questions related to this report, please contact the NCCIC at:

Email: NCCICCUSTOMERSERVICE@hq.dhs.gov
Toll Free: 1-888-282-0870

For industrial control systems cybersecurity information:  http://ics-cert.us-cert.gov 
or incident reporting:  https://ics-cert.us-cert.gov/Report-Incident?

The NCCIC continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.

Was this document helpful?  Yes  |  Somewhat  |  No

Back to Top