U.S. Flag Official website of the Department of Homeland Security
U.S. Department of Homeland Security Seal. ICS-CERT. Industrial Control Systems Cyber Emergency Response Team.
TLP:WHITE

Advisory (ICSA-18-058-03)

Emerson ControlWave Micro Process Automation Controller

Original release date: February 27, 2018

Legal Notice

All information products included in http://ics-cert.us-cert.gov are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see http://www.us-cert.gov/tlp/.



CVSS v3 7.5

ATTENTION: Remotely exploitable/low skill level to exploit.

Vendor: Emerson Process Management LLLP

Equipment: ControlWave Micro Process Automation Controller

Vulnerability: Stack-based Buffer Overflow

AFFECTED PRODUCTS

The following versions of ControlWave Micro firmware, a family of SCADA RTUs, PLCs, PACs, and flow computers, are affected:

  • ControlWave Micro [ProConOS v.4.01.280] – firmware: CWM v.05.78.00 and prior.

IMPACT

Exploitation may possibly cause a halt of Ethernet functionality, requiring a cold start to restore the system as well as communications related to ControlWave Designer access. This can possibly result in a loss of system availability and disruption in communications with other connected devices.

MITIGATION

Emerson offers the following mitigation advice:

  • Assess which ControlWave products in your organization have Ethernet connectivity.
  • Upgrade the affected devices to firmware version 05.79.00 to correct this possible action. System firmware upgrade instructions are available in product documentation (ControlWave Micro Process Automation Controller Instruction Manual, part D301392X012).
  • The resolution described is available only to the user when appropriately incorporated into the application running in ControlWave Micro firmware.
  • Prior to upgrading the system firmware, always perform a full alarm and historical collection (archive files as well as audit logs).

The release notes and firmware upgrade are available to registered users at the following link:

http://www3.emersonprocess.com/remote/support/v2/login.html.

NCCIC recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:

  • Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
  • When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.

NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available in the NCCIC Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT website.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.

No known public exploits specifically target this vulnerability.

VULNERABILITY OVERVIEW

A stack-based buffer overflow vulnerability caused by sending crafted packets on Port 20547 could force the PLC to change its state into halt mode.

CVE-2018-5452 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

RESEARCHER

Younes Dragoni of Nozomi Networks reported this vulnerability to NCCIC.

BACKGROUND

Critical Infrastructure Sectors: Energy, Water and Wastewater Systems

Countries/Areas Deployed: Worldwide

Company Headquarters Location: Minnesota, USA


Contact Information

For any questions related to this report, please contact the NCCIC at:

Email: NCCICCUSTOMERSERVICE@hq.dhs.gov
Toll Free: 1-888-282-0870

For industrial control systems cybersecurity information:  http://ics-cert.us-cert.gov 
or incident reporting:  https://ics-cert.us-cert.gov/Report-Incident?

The NCCIC continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.

Was this document helpful?  Yes  |  Somewhat  |  No

Back to Top