U.S. Flag Official website of the Department of Homeland Security
U.S. Department of Homeland Security Seal. ICS-CERT. Industrial Control Systems Cyber Emergency Response Team.
TLP:WHITE

Advisory (ICSA-18-046-03)

Schneider Electric IGSS Mobile

Original release date: February 15, 2018

Legal Notice

All information products included in http://ics-cert.us-cert.gov are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see http://www.us-cert.gov/tlp/.



CVSS v3 6.4

ATTENTION: Locally exploitable/low skill level to exploit.

Vendor: Schneider Electric

Equipment: IGSS Mobile

Vulnerabilities: Improper Certificate Validation, Plaintext Storage of a Password

AFFECTED PRODUCTS

Schneider Electric reports that the vulnerabilities affect the following IGSS Mobile products:

  • IGSS Mobile for Android, version 3.01 and all versions prior, and
  • IGSS Mobile for iOS, version 3.01 and all versions prior.

IMPACT

Successful exploitation of these vulnerabilities could allow an attacker to execute a man-in-the-middle attack. In addition, passwords can be accessed by unauthorized users.

MITIGATION

An update for Android with the fix for these vulnerabilities is available for download on Google Play:

https://play.google.com/store/apps/details?id=dk.schneiderelectric.igssmobile

An update for iOS with the fix for these vulnerabilities is available on Apple Store:

https://itunes.apple.com/dk/app/igss-mobile/id871698051

For more information on these vulnerabilities and associated patch, please see Schneider Electric’s security notification SEVD-2018-039-02 on their website:

https://www.schneider-electric.com/en/download/document/SEVD-2018-039-02/

NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available in the NCCIC Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT website.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.

In addition, NCCIC recommends that users take the following measures to protect themselves from social engineering attacks:

No known public exploits specifically target these vulnerabilities.

VULNERABILITY OVERVIEW

IGSS Mobile app lacks certificate pinning during the TLS/SSL connection establishing process. This issue could allow an attacker to execute a man-in-the-middle attack.

CVE-2017-9968 has been assigned to this vulnerability. A CVSS v3 base score of 6.4 has been calculated; the CVSS vector string is (AV:A/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:N).

IGSS Mobile app passwords are stored in clear-text in the configuration file.

CVE-2017-9969 has been assigned to this vulnerability. A CVSS v3 base score of 6.0 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:N).

RESEARCHER

Alexander Bolshev (IOActive) and Ivan Yushkevich (Embedi) reported these vulnerabilities to Schneider Electric.

BACKGROUND

Critical Infrastructure Sectors: Commercial Facilities, Critical Manufacturing, Energy

Countries/Areas Deployed: Worldwide

Company Headquarters Location: France


Contact Information

For any questions related to this report, please contact the NCCIC at:

Email: NCCICCUSTOMERSERVICE@hq.dhs.gov
Toll Free: 1-888-282-0870

For industrial control systems cybersecurity information:  http://ics-cert.us-cert.gov 
or incident reporting:  https://ics-cert.us-cert.gov/Report-Incident?

The NCCIC continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.

Was this document helpful?  Yes  |  Somewhat  |  No