U.S. Flag Official website of the Department of Homeland Security
U.S. Department of Homeland Security Seal. ICS-CERT. Industrial Control Systems Cyber Emergency Response Team.

Advisory (ICSA-17-129-02)

Siemens devices using the PROFINET Discovery and Configuration Protocol

Original release date: May 09, 2017

Legal Notice

All information products included in http://ics-cert.us-cert.gov are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see http://www.us-cert.gov/tlp/.



CVSS v3 6.5

ATTENTION: Exploitable from an adjacent network/low skill level to exploit.

Vendor: Siemens

Equipment: Devices using the PROFINET Discovery and Configuration Protocol (DCP)

Vulnerability: Denial of Service

AFFECTED PRODUCTS

Siemens reports that these vulnerabilities affect the following products using PROFINET DCP:

  • SIMATIC CP 343-1 Std, CP 343-1 Lean: All versions,
  • SIMATIC CP 343-1 Adv: All versions,
  • SIMATIC CP 443-1 Std, CP 443-1 Adv: All versions prior to V3.2.17,
  • SIMATIC CP 443-1 OPC-UA: All versions,
  • SIMATIC CP 1243-1: All versions,
  • SIMATIC CM 1542-1: All versions prior to V2.0,
  • SIMATIC CP 1543SP-1, CP 1542SP-1 and CP 1542SP-1 IRC: All versions,
  • SIMATIC CP 1543-1: All versions prior to V2.1,
  • SIMATIC RF650R, RF680R, RF685R: All versions prior to V3.0,
  • SIMATIC CP 1616, CP 1604, DK-16xx PN IO: All versions prior to V2.7,
  • SCALANCE X200: All versions,
  • SCALANCE X200 IRT: All versions,
  • SCALANCE X300, X408, X414: All versions,
  • SCALANCE XM400, XR500: All versions,
  • SCALANCE W700: All versions prior to V6.1,
  • SCALANCE M-800,S615: All versions,
  • Softnet PROFINET IO for PC-based Windows systems: All versions,
  • IE/PB-Link: All versions prior to V3.0,
  • IE/AS-i Link PN IO: All versions,
  • SIMATIC Teleservice Adapter Standard Modem, IE Basic, IE Advanced: All versions,
  • SITOP PSU8600 / UPS1600 PROFINET: All versions,
  • SIMATIC ET 200 Interface modules for PROFINET IO:
    • SIMATIC ET 200AL: All versions,
    • SIMATIC ET 200ecoPN: All versions,
    • SIMATIC ET 200M: All versions,
    • SIMATIC ET 200MP: All versions prior to V4.0.1,
    • SIMATIC ET 200pro: All versions,
    • SIMATIC ET 200S: All versions,
    • SIMATIC ET 200SP: All versions,
  • PN/PN Coupler: All versions,
  • Development/Evaluation Kits for PROFINET IO:
    • DK Standard Ethernet Controller: All versions prior to V4.1.1 Patch04,
    • EK-ERTEC 200P PN IO: All versions prior to V4.4.0 Patch01,
    • EK-ERTEC 200 PN IO: All versions prior to V4.2.1 Patch03,
  • SIMATIC S7-200 SMART: All versions,
  • SIMATIC S7-300 including F and T: All versions prior to V3.X.14,
  • SIMATIC S7-400 including F and H: All versions,
  • SIMATIC S7-1200 including F: All versions prior to V4.2.1,
  • SIMATIC S7-1500 including F, T, and TF: All versions prior to V2.1,
  • SIMATIC S7-1500 Software Controller including F: All versions prior to V2.1,
  • SIMATIC WinAC RTX 2010 including F: All versions,
  • SIRIUS ACT 3SU1 interface module PROFINET: All versions,
  • SIRIUS Soft starter 3RW44 PN: All versions,
  • SIRIUS Motor starter M200D PROFINET: All versions,
  • SIMOCODE pro V PROFINET : All versions,
  • SINAMICS:
    • SINAMICS DCM: All versions,
    • SINAMICS DCP: All versions,
    • SINAMICS G110M / G120(C/P/D) w. PN: All versions prior to V4.7 SP6 HF3,
    • SINAMICS G130 and G150: All versions prior to V4.8 HF4,
    • SINAMICS S110 w. PN: All versions,
    • SINAMICS S120: All versions prior to V4.8 HF4,
    • SINAMICS S150: All versions prior to V4.8 HF4,
    • SINAMICS V90 w. PN: All versions,
  • SIMOTION: All versions prior to V4.5 HF1,
  • SINUMERIK 828D:
    • V4.5 and prior: All versions,
    • V4.7: All versions prior to V4.7 SP4 HF1,
  • SINUMERIK 840D sl:
    • V4.5 and prior: All versions prior to V4.5 SP6 HF8,
    • V4.7: All versions prior to V4.7 SP4 HF1, and
  • SIMATIC HMI Comfort Panels, HMI Multi Panels, HMI Mobile Panels: All versions.

IMPACT

Successful exploitation of these vulnerabilities could cause the targeted device to enter a denial-of-service condition, which may require human interaction to recover the system.

MITIGATION

The attacker must have network access to the local Ethernet segment (Layer 2).

Siemens strongly recommends verifying that the affected products are protected as described in PROFINET Security Guidelines and Siemens Operational Guidelines in order to run the devices in a protected IT environment.

http://www.profibus.com/download/downloads/profinet-security-guideline/display/

https://www.siemens.com/cert/operational-guidelines-industrial-security

Siemens provides firmware updates fixing the vulnerabilities for the following affected products and recommends users update to the new fixed version:

  • SIMATIC CP 443-1 Std: Update to V3.2.17

https://support.industry.siemens.com/cs/ww/en/view/109745387

  • SIMATIC CP 443-1 Adv: Update to V3.2.17

https://support.industry.siemens.com/cs/ww/en/view/109745388

  • SIMATIC CM1542-1: Update to V2.0

https://support.industry.siemens.com/cs/ww/en/view/109744924

  • SIMATIC CP 1543-1: Update to V2.1

https://support.industry.siemens.com/cs/ww/en/view/109747253

  • SIMATIC RF650R, RF680R, RF685R: Update to V3.0

https://support.industry.siemens.com/cs/ww/en/view/109743740

  • SIMATIC CP 1616, CP 1604, DK-16xx PN IO: Update to V2.7

https://support.industry.siemens.com/cs/ww/en/view/109743058

  • SCALANCE W700: Update to V6.1.0

https://support.industry.siemens.com/cs/ww/en/view/109744953

  • IE/PB-Link: Upgrade to V3.0

https://support.industry.siemens.com/cs/ww/en/view/109744504

  • Development/Evaluation Kits for PROFINET IO:
    • DK Standard Ethernet Controller: All versions prior to V4.1.1 Patch04
    • EK-ERTEC 200P PN IO: All versions prior to V4.4.0 Patch01
    • EK-ERTEC 200 PN IO: All versions prior to V4.2.1 Patch03

Updates for Development/Evaluation Kits for PROFINET IO can be obtained via ComDeC at comdec@siemens.com or pic.industry@siemens.com

  • SIMATIC S7-300 including F and T: Update to V3.X.14

https://support.industry.siemens.com/cs/ww/de/ps/13752/dl or

https://support.industry.siemens.com/cs/ww/en/ps/13752/dl

  • SIMATIC S7-1200 including F: Update to V4.2

https://support.industry.siemens.com/cs/ww/en/view/109741461

  • SIMATIC S7-1500 including F, T and TF: Update to V2.1

https://support.industry.siemens.com/cs/ww/en/view/109478459

  • SIMATIC S7-1500 Software Controller including F: Update to V2.1

https://support.industry.siemens.com/cs/ww/en/view/109478528

  • SINAMICS:
    • SINAMICS G110M/G120(C/P/D) w. PN: Update to V4.7 SP6 HF3

https://support.industry.siemens.com/cs/ww/en/view/109482659

  • SINAMICS G130 and G150: V4.8: Update to V4.8 HF4

https://support.industry.siemens.com/cs/ww/en/view/109742040

  • SINAMICS S120: V4.8: Update to V4.8 HF4

https://support.industry.siemens.com/cs/de/en/view/109740193

  • SINAMICS S150: V4.8: Update to V4.8 HF4

https://support.industry.siemens.com/cs/ww/en/view/109742040

  • SIMOTION: Update to V4.5 HF1

https://support.industry.siemens.com/cs/ww/en/view/109742328

  • SINUMERIK 828D: V4.7: All versions prior to V4.7 SP4 HF1

SINUMERIK software can be obtained from the local Siemens account manager

  • SINUMERIK 840D sl:
    • V4.5 and prior: Update to V4.5 SP6 HF8
    • V4.7: Update to V4.7 SP4 HF1

SINUMERIK software can be obtained from the local Siemens account manager

Siemens is preparing updates for the remaining affected products and recommends the following mitigations in the meantime:

  • Apply cell protection concept
  • Use VPN for protecting network communication between cells
  • Apply Defense-in-Depth

As a general security measure Siemens and PNO strongly recommend protecting industrial control systems networks with appropriate mechanisms. Siemens encourages users to verify that the affected products are protected as described in PNO Security Guidelines and Siemens operational guidelines in order to run the devices in a protected IT environment.

https://www.siemens.com/cert/operational-guidelines-industrial-security

For more information on these vulnerabilities and more detailed mitigation instructions, please see Siemens Security Advisory SSA-293562 at the following location:

http://www.siemens.com/cert/en/cert-security-advisories.htm

ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available in the ICS‑CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.

No known public exploits specifically target these vulnerabilities.

VULNERABILITY OVERVIEW

Specially crafted PROFINET DCP broadcast packets could cause a denial-of-service condition of affected products on a local Ethernet segment (Layer 2). Human interaction is required to recover the systems. PROFIBUS interfaces are not affected.

CVE-2017-2680 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

Specially crafted PROFINET DCP packets sent on a local Ethernet segment (Layer 2) to an affected product could cause a denial-of-service condition in that product. Human interaction is required to recover the system. PROFIBUS interfaces are not affected.

This vulnerability affects only SIMATIC HMI Multi Panels and HMI Mobile Panels, and S7-300/S7-400 devices.

CVE-2017-2681 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).

RESEARCHER

Duan JinTong, Ma ShaoShuai, and Cheng Lei from NSFOCUS Security Team reported these vulnerabilities directly to Siemens.

BACKGROUND

Critical Infrastructure Sectors: Critical Manufacturing, Food and Agriculture, Chemical, Energy, Water and Wastewater Systems

Countries/Areas Deployed: Worldwide

Company Headquarters Location: Germany


Contact Information

For any questions related to this report, please contact ICS-CERT at:

Email: ics-cert@hq.dhs.gov
Toll Free: 1-877-776-7585
International Callers: (208) 526-0900

For industrial control systems security information and incident reporting: http://ics-cert.us-cert.gov

ICS-CERT continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.

Was this document helpful?  Yes  |  Somewhat  |  No