U.S. Flag Official website of the Department of Homeland Security
U.S. Department of Homeland Security Seal. ICS-CERT. Industrial Control Systems Cyber Emergency Response Team.
TLP:WHITE

Advisory (ICSA-16-082-01A)

Siemens APOGEE Insight Incorrect File Permissions Vulnerability (Update A)

Original release date: March 22, 2016 | Last revised: February 14, 2017

Legal Notice

All information products included in http://ics-cert.us-cert.gov are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see http://www.us-cert.gov/tlp/.



OVERVIEW

This updated advisory is a follow-up to the updated advisory titled ICSA-16-082-01 Siemens APOGEE Insight Incorrect File Permissions Vulnerability that was published March 22, 2016, on the NCCIC/ICS-CERT web site.

--------- Begin Update A Part 1 of 3 --------

Siemens has identified an incorrect file permissions vulnerability in APOGEE Insight. China Electronic Technology Cyber Security Co., Ltd. and Hunan Testing Institute of Product and Commodity Supervision reported this issue directly to Siemens. Siemens has released a new version to mitigate this vulnerability.

--------- End Update A Part 1 of 3 ----------

AFFECTED PRODUCTS

--------- Begin Update A Part 2 of 3 --------

Siemens reports that the vulnerability affects the following product:

  • APOGEE Insight: All versions prior to 3.15

--------- End Update A Part 2 of 3 ----------

IMPACT

This vulnerability could allow authenticated users of the operating system to modify application data for the affected product.

Impact to individual organizations depends on many factors that are unique to each organization. ICS-CERT recommends that organizations evaluate the impact of this vulnerability based on their operational environment, architecture, and product implementation.

BACKGROUND

Siemens is a multinational company headquartered in Munich, Germany.

The affected product, APOGEE Insight software, provides a graphical interface to manage and control buildings. According to Siemens, APOGEE Insight software is deployed across several sectors including Commercial Facilities. Siemens estimates that this product is used worldwide.

VULNERABILITY CHARACTERIZATION

VULNERABILITY OVERVIEW

INCORRECT DEFAULT PERMISSIONSa

The file permissions set for the APOGEE Insight application folder could allow authenticated operating system users to modify the APOGEE Insight application data if local access was obtained.

CVE-2016-3155b has been assigned to this vulnerability. A CVSS v3 base score of 3.4 has been calculated; the CVSS vector string is (CVSS:3.0/AV:L/AC:L/PR:H/UI:N/S:U/C:L/I:L/A:N).c

VULNERABILITY DETAILS

EXPLOITABILITY

This vulnerability is not exploitable remotely, and an attacker would need to be an authenticated user of the operating system.

EXISTENCE OF EXPLOIT

No known public exploits specifically target this vulnerability.

DIFFICULTY

An attacker with a low skill would be able to exploit this vulnerability.

MITIGATION

--------- Begin Update A Part 3 of 3 --------

Siemens has released a new APOGEE Insight version to resolve the vulnerability. Version 3.15 can be obtained by calling the local service organization. If users need assistance in identifying the local service organization, please call a local Siemens hotline center:

https://w3.siemens.com/aspa_app/

Until the new version can be applied, Siemens has detailed instructions on how to mitigate the vulnerability by correcting file permissions. To receive these instructions, users should contact their local service organization or a local Siemens hotline center.

--------- End Update A Part 3 of 3 ----------

For more information on this vulnerability and more detailed mitigation instructions, see Siemens Security Advisory SSA-151221 at the following location:

http://www.siemens.com/cert/en/cert-security-advisories.htm

ICS-CERT recommends that users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:

  • Limit access of authenticated users to only the machines that are needed.
  • Compartmentalize your network.
  • Restrict which programs a user can run.
  • Lock unattended machines.

ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available in the ICS‑CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.


Contact Information

For any questions related to this report, please contact the NCCIC at:

Email: NCCICCUSTOMERSERVICE@hq.dhs.gov
Toll Free: 1-888-282-0870

For industrial control systems cybersecurity information:  http://ics-cert.us-cert.gov 
or incident reporting:  https://ics-cert.us-cert.gov/Report-Incident?

The NCCIC continuously strives to improve its products and services. You can help by choosing one of the links below to provide feedback about this product.

Was this document helpful?  Yes  |  Somewhat  |  No